Water Treatment Pump Backup Power Condition Diagnostics

This demo stores ESS data from water treatment pump equipment in Machbase NEO and shows how thresholds, rates of rise, and pattern analysis help detect early signs of anomalies.

🎬 Demo |

🔗Source | 


This demo stores cell- and rack-level temperatures and voltages collected from the backup power system (ESS) of water treatment plant pumps in Machbase Neo. It shows how rate-of-rise and pattern analysis detect anomalies that thresholds alone miss. Since pumps must keep running during power outages, battery backup power remains on standby. Thermal runaway in a single cell can spread into a fire across the rack and immediately interrupt the water supply, making cell-level monitoring essential.


The system collects 98 tags at 1-second intervals, combining temperature and voltage from 4 racks and 48 cells with pump load. It loads 8.46 million records covering 24 hours in 28 seconds (approximately 300,000 records per second). The tag table stores site, rack, cell, and measurement type using the METADATA clause, allowing direct queries such as where rack='R02' and metric='TEMP' without parsing tag names as strings. Second-, minute-, and hour-level rollups are created automatically, delivering immediate aggregates while retaining all 8.46 million raw records.


Eight TQL scripts progressively extend detection from thresholds to rates of rise and anomaly patterns. A simple 55°C temperature threshold raises an alert for a one-second sensor spike while missing a cell undergoing thermal runaway. In contrast, the temperature rate of rise calculated from 5-minute rollups flags that cell as dangerous at 51.6°C, before it reaches the absolute threshold, based on a rise of 0.27°C per minute. A degraded cell whose voltage drops while its temperature remains normal is revealed only by trends in voltage differences between cells in the same rack. Comparing the maximum and average values over a one-minute interval distinguishes isolated sensor false alarms from sustained overheating.


Finally, a rule-based Health Score weights four risk factors: rate of rise, temperature, cell deviation, and voltage drop, and ranks all 48 cells in one table. The cell undergoing thermal runaway is rated Danger at 18.9, while the degraded cell with only a voltage drop is rated Caution at 74.0. Alongside each score, the main factors that reduced it are displayed, explaining how cells with the same risk level can have different underlying causes.


Learn how tag tables and TQL alone can detect equipment anomalies before thresholds are reached and display the reasons directly in a web interface, without setting up a separate analytics stack or preparing a trained model.